with strong load capacity
and easy scalability with all hot-swappable module design
Keep high efficiency operation at low load rate: 96% at 40% rated load and 95% at 20% rated load
of 50 KVA / 3U power module
easy installation and saving investment
Input power factor > 0.99, THDi < 3%, environment friendly and high-efficiency and energy-saving
50 Hz / 60 Hz frequency auto-sense, adapt to all kind of grid
improves generator matching up to 1:1.1
50 Hz input / 60 Hz output and 60 Hz input / 50 Hz output
enable UPS to operate efficiently at low load rate
support 4 units in parallel
Share battery pack in parallel operation, saving user’s battery cost
and battery configuration setting, battery number 30 ~ 46 pcs selectable
Intelligent charge / discharge management and float charging voltage temperature compensation, extending battery lifespan
and utility self boot
easy debugging and test on site
30% load can be driven when 2 fans fail and 50% load when 1 fan fails
top / bottom cable entry compatible
robust self-diagnostic function, and abundant event log for check
7 inches LCD touch screen, friendly human-machine interface
supports RS485 and dry contacts
|
MODEL |
|||
|
Rated capacity |
180KW / 200KVA |
||
|
Numbers of power modules |
4 |
||
|
Rated capacity of power module |
50KVA |
||
|
INPUT |
|||
|
Input wiring |
3Ph+N+PE |
||
|
Rated voltage |
380/400/415Vac |
||
|
Voltage range |
138 ~ 485 Vac (305 ~ 485 Vac without power downgrading; |
||
|
Input frequency |
40 ~ 70Hz |
||
|
Power factor |
≥ 0.99 |
||
|
Current distortion |
< 3% |
||
|
BATTERIES |
|||
|
Battery voltage |
± 240 Vdc (± 180, ± 192, ± 204, ± 216, ± 228, ± 252, ± 264, ± 276 selectable) |
||
|
Number of battery |
40 pcs12 V batteries (30 / 32 / 34 / 36 / 38 / 42 / 44 / 46 pcs selectable) |
||
|
OUTPUT |
|||
|
Output wiring |
3Ph+N+PE |
||
|
Rated voltage |
380 / 400 / 415 Vac ± 1% |
||
|
Frequency |
Synchronized with utility in mains power mode |
||
|
Power factor |
0.9 |
||
|
Voltage distortion |
≤ 1% with liner load / ≤ 3% with non-linear load |
||
|
Crest factor |
3:1 |
||
|
Inverter overload capacity |
105% < load ≤ 110%: transfer to bypass in 60 mins |
||
|
Bypass overload capacity |
Load ≤ 135% for long term; < 1000% load for 100ms |
||
|
SYSTEM |
|||
|
Efficiency |
96% |
||
|
Max. number of parallel |
4 units |
||
|
Transfer time |
0ms |
||
|
Protection |
Short circuit protection, overload protection, over-temperature protection, battery low voltage protection, output over/low voltage protection, fans failure protection etc. |
||
|
Communications |
RS485, dry contacts, SNMP |
||
|
Display |
7 inches LCD touch screen |
||
|
OTHERS |
|||
|
Operating temperature |
0 ~ 40°C |
||
|
Storage temperature |
-40°C ~ 70°C |
||
|
Humidity |
0 ~ 95% (non-condensing) |
||
|
Altitude |
≤ 1000m. Above 1000m, derating 1% for each additional 100m |
||
|
Protection level |
IP20 |
||
|
Noiselevel at 1 m |
< 65 dB |
||
|
Cabinet dimensions (WxDxH) (mm) |
600x850x2000 |
||
|
UPS module dimensions (WxDxH) (mm) |
442 x 620 x 130 |
||
|
Cabinetweight (kg) |
233 |
||
|
UPS module weight (kg) |
32 |
||