online double-conversion with DSP control
Thanks to the unity power factor to guarantee maximum real power
operation for all modules
easy installation and economic initial investment
50Hz / 60Hz auto sensing frequency
50Hz input / 60Hz output and 60Hz input / 50Hz output
Input Power Factor > 0.99, Input THDi ≤ 3%, Output THDV ≤ 5%
and redundancy technology easily set up different numbers of redundancy UPS module via LCD
40 x 12V/9AH for each module
in parallel operation, saving user’s battery cost
up to 160KVA/160KW constructed by each module 20KVA / 20KW, single charger module be equipped with 30 A charging current, 4 modules be configured maximally
and battery configuration setting, selectable battery number: 32 pcs / 34 pcs / 36pcs / 38 pcs / 40 pcs
prolong the working life of battery effectively
and mains auto restart
between key components and air duct effectively improve the system reliability
Fragile Components can be replaced easily as modules at low maintenance cost
top / bottom cable entry compatible
for hardware and software (C class lighting protection, circuit breaker, fuse, software and hardware protection), robust self detection, abundant event log for future check
5.7 inches LCD touch screen, friendly human machine interaction
Standard RS232 / USB / RS485 / Dry Contacts Communication Port
Optional SNMP communication port
|
MODEL |
|||
|
Capacity |
160 KW / 160 KVA |
||
|
Numbers of parallel module |
1 ~ 8 |
||
|
Numbers of redundancy module |
0 ~ 7 |
||
|
UPS power module |
20KVA / 20KW |
||
|
INPUT |
|||
|
Rated voltage |
380V/400V/415Vac |
||
|
Voltage range |
204 ~ 242 Vac (load ≤ 50%); |
||
|
Rated frequency |
50 / 60 Hz (auto-sense) |
||
|
Frequency range |
40 ~ 70 Hz |
||
|
Power factor |
≥ 0.99 |
||
|
Total harmonic distortion (THDI) |
≤ 3% |
||
|
Bypass voltage range |
Rated output voltage - 40% ~ rated output voltage + 20% (settable via LCD) |
||
|
OUTPUT |
|||
|
Voltage |
380V / 400V / 415 Vac |
||
|
Voltage regulation |
± 1% |
||
|
Frequency |
Synchronized with utility in mains mode; |
||
|
Power factor |
1.0 |
||
|
Waveform |
Pure sine wave |
||
|
Crest factor |
3:1 |
||
|
Total harmonic distortion(THDV) |
≤ 1% (linear load); ≤ 5% (non-linear load) |
||
|
Transfer time |
0ms |
||
|
Inverter overload capability |
110% ~ 130%: transfer to bypass in 10 mins; |
||
|
Bypass overload capability |
≤ 150%: long time running |
||
|
BATTERIES |
|||
|
DC voltage |
± 240 Vdc (options: ± 192 Vdc / ± 204 Vdc / ± 216 Vdc / ± 228 Vdc) |
||
|
Inbuilt battery of standard model |
40 x 12V/9Ah for each module |
||
|
Charging current |
1 ~ 30A / 60A (settable via LCD) |
||
|
SYSTEM |
|||
|
Efficiency |
≥ 94% |
||
|
Display panel |
5.7 Inches LCD touch screen |
||
|
Alarm |
Battery mode, low battery, fans fault etc. |
||
|
EMI |
EN62040-2 |
||
|
EMS |
IEC61000-4-2 (ESD) |
||
|
COMMUNICATIONS |
|||
|
RS232 / RS485 / USB / dry contacts (standard) |
Supports Windows® 98/2000/2003/XP/Vista/2008/7/8/10 |
||
|
SNMP (option) |
Power management from SNMP manager and web browser |
||
|
OTHERS |
|||
|
Humidity |
0 ~ 95% RH @ 0 ~ 40°C (non-condensing) |
||
|
Noise level |
≤ 60dB |
||
|
Module dimensions (mm) WxDxH |
482x590x131 |
||
|
Module weight |
28kg / power module, 27kg / charger module, 7kg / monitoring module |
||
|
UPS dimensions (mm) WxDxH |
600x1000x2000 |
||
|
UPS packaged dimensions (mm) WxDxH |
700x1070x2160 |
||
|
UPS Net/Gross weight (kg) |
290 / 310 |
||
|
Input / output / bypass breaker |
Yes |
||